Absorption
machines :
1. HOT WATER FIRED
Features
|
|
CAPACITY
:
the
supermax hot water fired chillers , achieving chilled water
temperature
upto 4.5 C, are available in the following range :
low
Temperature (LT) : 65 - 650
TR
Medium
Temperature (MT) : 88 - 1400 TR
high
Temperature (HT) : 90 - 1385 TR
|
|
Operating
hot Water Temperatures :
Low
Temperature (LT) : 70 C - 100 C
Medium
Temperature (MT) : 110 C 150 C
High
Temperature (HT) : 150 C - 200 C |
|
10
- 100% stepless Modulation :
3-way
diverting valve automatically varies hot water flow .
in
order to maintain
the temperture
of leaving
chilled
water , for cooling loads ranging from 10% to 100%
of
the designed capacity of the chiller.
|
|
Auto
De-Crystallization :
the
supermax chillers are installed with unique auto de-crystallization
circuit to eliminate crystallization.
|
|
On-line
purging :
the
factory mounted and tested purging unit consists of an electrical motor
driven purge pump ,storage
tank
, necessary piping and valves . any non-condensable gas generated in the
chiller during operation ,
is
purged contiuosly into the storage tank , thereby maintaing low vacum in
the shell.
|
|
Side
exit nozzies :
the
absorber , evaporator and condenser headers are provided with side exit
nozzles for ease of
maintenance
and lower down-time . the absorber and condencer headers are hinged type
, for easy
access
to the tube bundle and eliminate need for heavy lifting arrangement .
|
|
Gravty
Feed System :
the
supermax chillers ues graving feed , non-pressurised super - spraying
system , for spraying refrigerant
and
absorbent . this avoids the use of nozzles , which have the problems of
clogging abd water & tear.
|
|
Croos-over
Piping :
the
cross-over piping from absorber to condenser is a standarfeature in
Supermax vapour absorption
chillers
. It reduces the piping work , welding . ect . at site .
|
|
Isolation
Valves for Pumps :
isolation
valves provided on the pumps , facilitate on-line pump maintenance ,
without breaking the
vacuum
in the Supermax vapour absorpation chiller.
|
|
Corrosion
Inhibitors :
Super
active uses the new generation corrosion inhabitor , Lithium Molybdate
which is more effective than
Lithium
Nitrate and Lithium Chromate , which are conventionally used .
|
|

|