manager director

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Absorption machines :

1. HOT WATER FIRED

Features     

 

 

CAPACITY :

the supermax hot water fired chillers , achieving chilled water

temperature upto 4.5 C, are available in the following range :

low Temperature (LT)  : 65 - 650 TR

Medium Temperature (MT) : 88 - 1400 TR

high  Temperature (HT) : 90 - 1385 TR

 

Operating hot Water Temperatures :

Low Temperature (LT) : 70 C - 100  C

Medium Temperature (MT) : 110 C 150 C

High Temperature (HT) : 150 C - 200  C

 

10 - 100% stepless Modulation :

3-way diverting  valve  automatically varies hot water flow .

 in    order  to   maintain      the    temperture    of     leaving

chilled water , for cooling loads ranging from 10% to 100%

of  the designed  capacity  of the  chiller.

 

Auto De-Crystallization :

the supermax chillers are installed with unique auto de-crystallization circuit to eliminate crystallization.

 

On-line purging :

the factory mounted and tested purging unit consists of an electrical motor driven purge pump ,storage

tank , necessary piping and valves . any non-condensable gas generated in the chiller during operation ,

is purged contiuosly into the storage tank , thereby maintaing low vacum in the shell.

Side exit nozzies :

the absorber , evaporator and condenser headers are provided with side exit nozzles for ease of

maintenance and lower down-time . the absorber and condencer headers are hinged type , for easy

access to the tube bundle and eliminate need for heavy lifting arrangement .

 

Gravty Feed System :

the supermax chillers ues graving feed , non-pressurised super - spraying system , for spraying refrigerant

and absorbent . this avoids the use of nozzles , which have the problems of clogging abd water & tear.

 

Croos-over Piping :

the cross-over piping from absorber to condenser is a standarfeature in Supermax vapour absorption

chillers . It reduces the piping work , welding . ect . at site .

 

Isolation Valves for Pumps :

isolation valves provided on the pumps , facilitate on-line pump maintenance , without breaking the

vacuum in the Supermax vapour absorpation chiller.

 

Corrosion Inhibitors :

Super active uses the new generation corrosion inhabitor , Lithium Molybdate which is more effective than

Lithium Nitrate and Lithium Chromate , which are conventionally used .